PRESSURE SWITCH (shield)-SD-PS1001

FACTORY SETTING

  • SD-PS1001 / SD-PS1002 : 4-8 PSI
  • SD-PS4001 : Operates at decreasing pressure at 30 PSI
  • SD-PS4002 : Operates at increasing pressure at 50 PSI and decreasing pressure at 30 PSI
  • SD-PS12001 : Operates at decreasing pressure at 110 PSI
  • SD-PS12002 : Operates at increasing pressure at 130 PSI and decreasing pressure at 30 PSI

APPROXIMATE DIFFERENTIAL

  • SD-PS1001/SD-PS1002: 3 PSI throughout range
  • SD-PS4001/SD-PS4002 : 3 PSI @ 10 PSI & 6 PSI @ 100PSI
  • SD-PS12001/SD-PS12002 : 3 PSI @ 10 PSI & 9 PSI @ 200 PSI
  • Pressure Connection: ½˝ NPT male glass reinforced nylon
  • Contact Rating: 10 A @125/250 VAC 2.5 A @ 30VDC
  • Temperature Range: -40°F to 140°F (-40°C to 60°C)

SERVICE USE

  • Automatic Sprinkler: NFPA 13
  • One or Two Family Dwelling: NFPA 13D
  • Residential Occupancies up to 4 Stories: NFPA 13R
  • National Fire Alarm Code: NFPA 72

Description

SD-PS1001, The SD-PS Series Pressure Switches shall be installed on the sprinkler system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type. Switches shall have a maximum service pressure rating of 300 psi and shall be factory adjusted to operate at a pressure of 4 – 8 psi. There shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @ 125/250 VAC and 2.5 Amp @ 30 VDC. The contractor shall furnish and install, where indicated on the plans, pressure switches according to appropriate NFPA standards. Switches shall be provided with a ½˝ NPT male pressure connection to be connected to the alarm check valve of a “wet” sprinkler system, into the intermediate chamber of a “dry” system, or to a pre-action or deluge valve. They shall be activated by any flow of water equal to or in excess of the discharge from one sprinkler head. Switches shall provide 1 knockout type and 1 open hole for ½˝ conduit fitting attachment and a ground screw provision for electrical grounding. The switch enclosure shall be weatherproof. The cover shall incorporate tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc. and approved by Factory Mutual.

Features

  • Sensitivity adjustment wheel, no special tools required
  • Reinforced diaphragm resists pressure spikes
  • Two conduit entrances
  • Both one- and two-switch models available Specifications
  • Maximum Operating Pressure: 300psi

 

Reviews