K FACTOR 11.2(GXLO Series)

Model GXLO Standard Response Automatic Sprinklers

Recommended CSI Master Format Specification Location: 21 13 00, Fire Suppression Sprinkler Systems (formerly 13930)

Sprinklers shall be standard response [upright] [FM only: pendent] sprinklers that are [FM Approved] [UL Listed]. Sprinkler frame and deflector shall be of bronze construction, utilizing a levered fusible alloy solder link and having a [¾” NPT] [ISO 7-1R¾] thread.  Water seal assembly shall consist of a Teflon-coated Belleville spring washer containing no plastic parts. Sprinkler temperature rating shall be [165°F (74°C)] [212°F (100°C)] [286°F (141°C)].  Sprinklers shall have a nominal K-factor of 11.2 gpm/psi1/2 (160 l/min/bar1/2) – extra-large orifice. Sprinklers shall have a rated working pressure of 175 psi (12 bar).

Sprinklers shall be of the Model GXLO Series. Refer to Reliable Bulletin 129 for associated sprinkler information.

Style: Upright, Intermediate Upright

Threads: 3/4” NPT or ISO 7-1R3/4*

Nominal K-Factor: 11.2 (160 metric)

Max. Working Pressure: 175 psi (12 bar)

Material Specifications

Thermal Sensor: Solder Capsule

Sprinkler Frame: Brass Alloy

Button/Cup: Brass Alloy

Sealing Assembly: Brass with PTFE

Load Screw: Bronze

Deflector: Bronze Alloy

Levers: Bronze Alloy

Ejection Spring: Stainless Steel

Category:

Description

We provide Reliable Model GXLO (extra-large orifice) upright and pendent sprinklers for Pump room. These are standard coverage standard-response sprinklers that utilize a robust center strut, solder in compression thermal element. These sprinklers are intended for use in hydraulically calculated control mode density area (CMDA) storage and non-storage occupancies in accordance with the area/density curves of NFPA 13 or other applicable standards.

The Model GXLO sprinkler is FM & UL Approved as a standard response storage and non-storage sprinkler when used in accordance with FM Global Property Loss Prevention Data Sheets.

For new installations, the sprinkler is provided with either 3/4-inch NPT or ISO 7-R3/4 threads. The upright version is also available with 1/2-inch NPT or ISO 7-R1/2 threads for retrofit installations only. Sprinklers without guards are installed using the Model H wrench.

For use as an intermediate level sprinkler, the Model GXLO upright sprinkler is available with a factory installed water shield. Various other water shields, guards, or guard/shield options are also available for both upright and pendent models (please refer to Technical Specifications on following pages). Sprinkler guards or guard/shields may be installed in the field or factory installed. Use of the Model JV sprinkler wrench is required for installation where a guard is added to the sprinkler prior to threading the assembly into a fitting.