FOAM SUPPRESSION SYSTEM

TECHNICAL INFORMATION

 

Tank Shell Carbon Steel, SA 516 Gr.70.
Bladder Vinyl Based Polymer
Pressure Relief Valve (Optional) Brass Construction with Set Pressure @ 15 bar
Internal Piping Perforated PVC, sch. 80,
Flanges ASTM A105, Class 150
Water Pipe Carbon Steel. sch. 40.
Foam Pipes Stainless Steel. sch. 40.
Vent/Drain/NRV Valves Brass/Bronze.
Sight Glass Valve Sight Gauge with Shut Off & Drain Valve
Painting External Zinc Rich Primer with Red Enamel Finish
Painting Internal Zinc Rich Primer with Coal Tar Epoxy Paint

DESIGN DATA

Tank mounting Vertical
Concentrate Storage Capacity 50-1200 Gallon (see tables)
Flow Range 78 – 9500 LPM
Foam Concentrate AFFF 3%,6%
Design Pressure 175PSI (12.09 bar)
Test Pressure 227PSI (15.69 bar)
Ratio Controller Size 2½”,3″, 4” & 6”
Storage Temperature +2°C – +49°C
Foam Concentrate Proportioning Orifice 3%, 6%

*NOTE: The UL listing does not include proportioning of 6% Foam Concentrate and 2½” Ratio Controller


 RATIO CONTROLLER DETAILS

SIZE INLET / OUTLET FLANGE LENGTH

(mm)

ORIFICE DIA. (mm)
3% 6%
65NB  

 

ANSI CLASS 150

190 6.9 9.5
80NB 266 10.7 15.04
100NB 332 15.7 21
150NB 342 28.7 44.5

RATIO CONTROLLER SIZE & FLOW RATE

SIZE FLOW RATE , 3%

(as per UL)

FLOW RATE , 3%

(as per FM)

FLOW RATE, 6%

(as per FM)

65NB 100 – 1550 LPM 78 – 1036 LPM 159 – 984 LPM
80NB 260 – 3000 LPM 270 – 3000 LPM 270 – 3000 LPM
100NB 650 – 6000 LPM 660 – 5750 LPM 633 – 3922 LPM
150NB 1200 – 12000 LPM 1090 – 9530 LPM 674 – 4012 LPM

Description

Fire suppression foam comprises three parts: foam concentrate, water, and air. When mixed correctly, these parts form a homogeneous foam blanket that extinguishes flames by the combined cooling mechanisms, separating the flame source from the product surface, suppressing vapors, and smothering. This makes foam suppression systems an effective option for protecting flammable and combustible liquids.

NAFFCO Pre-piped Vertical Bladder Tank is a complete self-contained proportioning system consisting of a bladder tank, ratio controller, and assembled piping. It is designed to inject foam concentrate into the water supply of a fire protection system and automatically proportions over a wide range of flow and pressures without the use of external power supply. NAFFCO Pre-piped Vertical Bladder Tank utilize water supply to pressurize the bladder and force the foam concentrate into the ratio controller. Once the system is in operation, water supply simultaneously feeds the bladder tank and ratio controller. The water applied to the outside surface of the bladder will subsequently displace the foam concentrate contained inside the bladder through the foam outlet pipe and into the metering orifice of the ratio controller. The water flowing through the ratio controller will create a low-pressure area between its inlet nozzle and to its downs stream section. The low-pressure causes the foam concentrate to flow proportionately to the water flow through the metering orifice. This ensures correct proportioning of the foam concentrate and water over a wide range of flow conditions.