• PHYSICAL PROPERTIES OF IG-01

    Chemical Name Ar (Argon)
    Molecular Weight 39.9
    Boiling Point at 1.013 Bar -185.9°C
    Critical Pressure 49 Bar
    Critical Temperature -122.3°C
    Design Concentration for Class A Fire (NFPA) 38.7%
    Flooding Factor for Class A Fire (NFPA) 0.481 m³/ m³
    NOAEL 43%
    LOAEL 53%

     

    PHYSICAL PROPERTIES OF IG - 100

    Chemical Name N² (Nitrogen)
    Molecular Weight 28
    Boiling Point at 1 ATM (1.013 Bar) -196°C
    Critical Pressure 40 Bar
    Critical Temperature -146.9°C
    Design Concentration for Class A Fire (NFPA) 37.2%
    Flooding Factor for Class A Fire (NFPA) 0.457 m³/ m³
    NOAEL 43%
    LOAEL 53%

     

    PHYSICAL PROPERTIES OF IG - 55

    Chemical Name N²/Ar
    Molecular Weight 33.95
    Boiling Point at 760 mm Hg -190.1ºC
    Critical Pressure 602 psia
    Critical Temperature -134.7ºC
    Design Concentration for Class A Fire (NFPA) 37.2%
    Flooding Factor for Class A Fire (NFPA) 0.457 m³/ m³
    NOAEL 43%
    LOAEL 52%

     

    PHYSICAL PROPERTIES OF IG - 541

    Chemical Name N²/Ar/CO²
    Molecular Weight 34
    Boiling Point at 1 ATM (1.013 Bar) -196ºC
    Critical Pressure N/A
    Critical Temperature N/A
    Design Concentration for Class A Fire (NFPA) 37.2%
    Flooding Factor for Class A Fire (NFPA) 0.457 m³/ m³
    NOAEL 43%
    LOAEL 52%
  • Shield Novec 1230 Clean Agent Fire Suppression Systems are highly efficient when combined with a properly designed plumbing network using the Shield version of the VDS Flow Calculation Software.

    COMPONENTS

    1. Cylinders:cylinders are manufactured in accordance with DOT 4BW500 and TC BWM34* standards. *490L cylinder assemblies are only DOT T4BW500 compliant.
    2. Valve Assembly:All valves are of the pressure differential design, and will not operate without deliberate actuation. The actuation devices can be removed while under pressure to facilitate functionality testing of the system. It is also equipped with a monitoring Pressure Switch as well as a port to facilitate pneumatic actuation of secondary cylinder assemblies.
    3. Cylinder Straps:The cylinder body straps are designed to secure the system assembly during discharge. A single strap is included with all systems up to 103L, while larger systems are equipped with two straps. Systems 490L in size are shipped with two wall mount straps, floor mount straps are available upon request.
  • PHYSICAL PROPERTIES

    Chemical Name Heptafluoropropane (CF3CHFCF3)
    Molecular Weight 170.03
    Boiling Point @ 760 mm Hg 3.9°F (-15.6°C)
    Freezing Point -204°F (-131.1°C)
    Critical Temperature 215°F (101.7°C)
    Critical Pressure (psia) 422 psia (2912 kPa)
    Critical Volume (ft3/lbm) (cc/mole) 0.0258 (274)
    Critical Density (lbm/ft3) 38.8 (621 kg/m3)
    Specific Heat, Liquid (BTU/lb-F°) @ 77°F (25°C) 0.283 (1.184 kj/kg/°C)
    Specific Heat, Vapor (BTU/lb-°F) @ constant pressure of 1 ATM @ 77l F (25l c) 0.1932 (0.808 kj/kg/°C)
    Heat of Vaporization (BTU/lb) at Boiling Point 57.0 (132.6 kj/kg)
    Thermal Conductivity (BTU/h ft°F) of Liquid @ 77°F (25°C) 0.040 (0.069 w/m°C)
    Viscosity, Liquid (lb/ft/hr) @ 77°F (24°C) 0.443 (0.184 centipoise)
    Vapor Pressure (psia) @ 77°F (25°C) 66.4 (457.7 kPa)
    Ozone Depletion Potential 0
    Estimated Atmospheric Lifetime (years) 31 - 41
    LC50 (Rats; 4hrs - ppm) >788,000
Go to Top