• FUEL TANK CAPACITY

    Type Cylindrical, Horizontal
    Fuel Tank Size 70 - 750 US Gallons
    1000 - 2000 US Gallons * *

    * * With Pad Plate & ladder

    FEATURES

    • Meets NFPA 30 requirements.
    • Sized as specified by NFPA 20 for fire pump applications.
    • Designed and Fabricated in accordance with UL 142 (Steel Aboveground Tanks for Flammable and Combustible Liquids) standard.
    • Tested for tightness against leakage.
    • Top quality fittings and fabrication materials.
    • Sturdy lifting lug and legs.
    • Vent opening to prevent build-up of pressure or vacuum inside the tank during filling, emptying or due to atmospheric temperature changes.
    • Approved welding process.
  • RATINGS
    Power Rating 1.5 - 7.5 HP DOL Starter & 10 - 40 HP Star Delta Starter
    Voltage 230/380/415/480 V
    Frequency 50/60 hz
    FEATURES  ENCLOSURE OPTIONS: NEMA 2, NEMA 3, NEMA 4, NEMA 4x, NEMA 12 STANDARD FEATURES
    • Main disconnect switch with rotary handle, sized for disconnecting motor horsepower and voltage.
    • Motor Starter (DOL) or Overload Relay (Star-Delta) rated to the motor's horsepower, with thermal and short circuit protection.
    • Rated motor connectors.
    • Circuit breaker for protection of control circuit and motor.
    • Star—Delta starting timer. (in Model NFY-JSD1 & NFYJSD1-M1)
    • Power ON/Healthy indicator/free contact.
    • Pump Run indicator/free contact.
    • Pump Trip indicator/free contact.
    • Adjustable pressure switch.
    • Run Period Timer
    MODELS: NFY-JDO1 Direct On-Line & NFY-JSD1 Star-Delta. Selector switch for Hand-Off-Automatic Operation. NFY-JDO1-M1 Direct On-Line & NFY-JSD1-M1 Star-Delta
    • Touch control panel to operate, monitor, and set up the controller.
    • Automatic and manual selection on the touch panel screen.
    • Real-time voltage and pressure reading on screen.
    • Real-time pump running status, alarm details, and time delay on screen.
    • Password protection.
    • Screen saver mode.
    • Up to 4 auxiliary inputs and 3 output ports.
    • Up to 5 predefined options to select on input auxiliary.
    • Up to 24 predefined options to select on output auxiliary
  • SPECIFICATION

    MODEL - STARTING TYPE

    • NFY-DOM1 - Direct On Line
    Motor Power (HP0 Rated Voltage (V) Frequency (Hz) Rated Circuit(A) Short Circuit(kA)
    15 380 - 415 50 / 60 27 100
    20 380 - 415 50 / 60 34 100
    25 380 - 415 50 / 60 44 100
    30 380 - 415 50 / 60 51 100
    40 380 - 415 50 / 60 66 100
    50 380 - 415 50 / 60 83 100
    50 380 - 415 50 / 60 103 100
    75 380 - 415 50 / 60 128 100
    100 380 - 415 50 / 60 165 100
  • SPECIFICATION

    DC Voltage(VDC) Line Voltage(VAC) Enclosure Size(mm)
    12 220/110 900 (H) x 600 (W) x 300 (D)
    24 220/110 900 (H) x 600 (W) x 300 (D)
  • RATINGS SERIES: NM, TEFC ENCLOSURE 2 POLE
    Rated Output 10 HP - 500 HP
    Rated Voltage 380-400-415v (50Hz), 208-230v* (60Hz), 380-400v (60Hz), 440-460v (60Hz) & 575 (60Hz)
    Rated Speed 2923 - 2980 (50Hz) & 3506 - 3575 (60Hz)
    *Motors rated at this voltage are available only for power ratings from 15 to 100 Hp. 4 POLE
    Rated Output 10 HP - 400 HP
    Rated Voltage 380-415v (50Hz), 208-230v* (60Hz), 380-400v (60Hz), 460v (60Hz) & 575v (60Hz)
    Rated Speed 1460-1480 RPM (50Hz) & 1750 -1780 RPM (60Hz)
    ** Motors rated at this voltage are available only for power ratings from 15 to 100 Hp.
  • SPECIFICATION DIESEL ENGINE RANGES (SERIES: FD - R / FD - H / FD - HN / FD – HT / FD-Hi)
    Rated Output 10 HP - 500 HP
    Rated Voltage 380-400-415v (50Hz), 208-230v* (60Hz), 380-400v (60Hz), 440-460v (60Hz) & 575 (60Hz)
    Rated Speed 2923 - 2980 (50Hz) & 3506 - 3575 (60Hz)
    * These values only indicate the overall range available in this series. For the availability of any specific ratings and details of its certification, please contact the factory.
  • FEATURES 

    • Performance characteristics as per NFPA 20
    • Complete unit responsibility.
    • Complete in-house fabrication capabilities.
    • Hydrostatic testing facilities.
    • Operation run test as per NFPA 20.
    • Vertical Turbine models pumps for capacities up to 6000 USGPM.
    • Drivers: Electric motor drive or diesel engine drive.
    • Electrical testing capabilities for motors and controllers connected to fire pumps as per NFPA standards.
    • Capable of supplying additional accessories wherever required.
  • FEATURES

    • Performance characteristics as per NFPA 20
    • Complete unit responsibility.
    • Complete in-house fabrication capabilities.
    • Hydrostatic testing facilities.
    • Operation run test as per NFPA 20.
    • Horizontal End Suction pumps for capacities up to 750 USGPM
    • Drivers: Electric motor drive or diesel engine drive.
    • Electrical testing capabilities for motors and controllers connected to fire pumps as per NFPA standards.
    • Capable of supplying additional accessories wherever required.
  • FEATURES Performance characteristics as per NFPA 20 Complete unit responsibility. Complete in-house fabrication capabilities. Hydrostatic testing facilities. Operation run test as per NFPA 20. Horizontal Split case pumps for capacities up to 8000 USGPM. Drivers: Electric motor drive or diesel engine drive. Electrical testing capabilities for motors and controllers connected to fire pumps as per NFPA standards. Capable to supply additional accessories wherever required
Go to Top